Hot plug availability
|
(6) Fans
|
Maximum Power Consumption
|
2000 Watts Max
|
Power Input Redundancy
|
Yes, with auto failover switch
|
Power Input Single Phase
|
Yes
|
Rated Line Current
|
15 A per line cord
|
Required Power Supply
|
208-240 VAC + - 10%
|
Electrical Connectivity
|
NEMA L6-20P
|
Circuit Breaker Rating
|
20A per line cord
|
Air Flow
|
2500 CFM Max @ 208 VAC
|
Air Temperature Regulation
|
Yes
|
Air Temperature to Servers
|
Settable, suggested at 68-77 ° F ( 20-25° C)
|
Maximum Cooling Capacity
|
35kW (Bi-directional 17.5kW per side)
|
Chilled Water Connections
|
1.00 in (25.4 mm)
|
Condensate Evacuation Tube
|
Yes
|
Cooling Rack Front Door
|
Transparent polycarbonate insert behind mesh
|
Cooling Rack Rear Door
|
Solid, no mesh
|
Cooling Agent
|
Primary or auxiliary chilled water supply
|
Coupling Type
|
1.00 in NPT or BSPP (G type) supplied in Main Hose Kit AF027A
|
Maximum Current
|
54 A peak for 20 ms per line cord
|
Minimum Dropout Carry Through Time
|
20 ms
|
Dynamic Load
|
2000 lbs (908 kg) of IT equipment
|
Environmental Monitoring
|
Air temperature to servers control - Yes Male, tapered
|
Pipe Thread
|
Male, tapered
|
Recommended Chilled Water Inlet
|
45.0 ° F ( 7.00 ° C) 7° to 15° C (of IT equipment)
|
Static Load
|
2000 lbs (908 kg)of IT equipment
|
Water Connection Size
|
1.00 in (25.4 mm)
|
MCS Mounting Location
|
Left hand side
|
Communications Management
|
Multi-function LCD status and control console
|
Side Panels Included
|
Yes
|
Dimensions (W x D x H)
|
78.7 x 35.8 x 51 in (199.89 x 60.96 x 129.54 cm)
|
Weight
|
1080 lb (513kg) (2000 lbs (908 kg) of IT equipment)
|
Maximum Operating Humidity Range
|
Allowable 20%-80% Recommended 40%-55%
|
Maximum operating temperature (Fahrenheit)
|
41.0 ° F Min
95.0 ° F Max
|
Maximum operating temperature (Celsius)
|
5° C Min
35.00 ° C Max
|
Industry Compliance Certifications
|
UL Listing 484, CUL Canadian std. 22.2 No.236 EN61000-3-2 EN61000-3-3 Flicker EN61000-4-2 EN61000-4-3 EN61000-4-4 EN61000-4-5 EN61000-4-6 EN61000-4-8 EN61000-4-11 CB report to IEC 60950-1 TÜV / GS EN 60335-1 (according to 60335-2-40)
|
Warranty
|
HP Modular Cooling System: One year warranty, parts only (1-0-0)
HP 10642 G2 Series Rack: Three year warranty, parts only (3-0-0)
NOTE: Certain restrictions and exclusions apply. Consult the HP Customer Support Center for details.
|
Warranty Options
|
Standard MCS G2 Warranty 1-0-0 Standard Rack Warranty 3-0-0
|