| System features |
Operating voltage
|
220, 230, 240V models
|
Electrical input connection
|
IEC-309 32Amp, 3m cord
|
Electrical input REPO
|
Remote Emergency Power-Off disables AC power to load
|
Electrical output connections
|
LS1: 15A CB -> 2 x C19 + 2 x C13; LS2: 15A CB -> 2 x C19 + 2 x C13; Plus one pigtailed receptacle (LS1) 1 x IEC-309 32Amp for International model
|
Battery type
|
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
|
Communications serial ports
|
Standard DB-9 ports (ships with communication cable)
|
Communications option slot
|
One
|
Communications option cards
|
Six Port Card and SNMP / Serial Port Card
|
LED indicators
|
LED and switch membrane integrated into the front panel; with four-button control (three buttons for UPS power control and one button under the front bezel for configuration).
|
Communications software
|
Online power management software (SNMP)
|
Safety
|
GS, CE, GOST (Safety Markings); UL1778, UL60950-1; CSA22.2 No.107.3, No.60-1950; EN50091-1-1; EN60950-1 IEC62040-1-1 (Safety Certifications)
|
Extended runtime modules (amount)
|
2
|
Load segments
|
3
|
Hot-swap batteries
|
yes
|
Product dimensions (W x D x H)
|
13.0 x 66.0 x 44.5 cm
|
Package dimensions (W x D x H)
|
35.6 x 97.8 x 81.3 cm
|
Product weight
|
73 kg
|
Package weight
|
91 kg
|
Operating humidity range
|
20 to 80% non-condensing
|
Non-operating humidity
|
5 to 95%
|
Operating altitude
|
Up to 6,562 ft (2000 m) above sea level
|
Non-operating altitude
|
49,212 ft (15,000 m) above sea level
|