| System features |
Warranty
|
HP Modular Cooling System: One year warranty, parts only (1-0-0); HP 10642 G2 Series Rack: Three year warranty, parts only (3-0-0)
|
Service & support options
|
Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical. A full range of HP Care Pack hardware and software services are available including: Installation and start up; Education courses; Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair; Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and VMware-base d IT solutions helping to deliver high level of application availability. Response times range from 30 mins for critical problems to 2 hours; System Management, Performance Services and Mission Critical Support Solution
|
Product dimensions (W x D x H)
|
Rack: 90.9 x 127.0 x 200.0 cm; Expansion Rack: 60.0 x 127.0 x 200.0 cm
|
Package dimensions (W x D x H)
|
122.0 x 177.8 x 224.8 cm
|
Product weight
|
Rack: 540 kg; Expansion Rack: 115 kg
|
Package weight
|
Rack: 621.4 kg; Expansion Rack: 129 kg
|
Static load
|
908 kg
|
Hot-Plug support
|
Heat exchangers: 1; Fans: 6
|
Cooling agent
|
Primary or auxiliary chilled water supply
|
Condensate evacuation tube
|
Yes
|
Air temperature regulation
|
Yes
|
Cooling - rack front door
|
Transparent polycarbonate insert behind mesh
|
Cooling - rack rear doors (split)
|
Solid, no mesh
|
Chilled water connections
|
Bottom rear
|
MCS mounting location
|
Left hand side
|
Maximum cooling capacity
|
35 KW
|
Recommended chilled water inlet temperature
|
7.0° C
|
Maximum chilled water flow rate
|
1.00 lps
|
Water connections
|
25.4 mm
|
Coupling type
|
25.4 mm NPT or BSPP (G type) supplied in Main Hose Kit AFxxxxA
|
Pipe thread
|
Male, tapered
|
Power requirements
|
208-240 VAC (+/- 10%); 50/60 Hz
|
Power consumption
|
2000 Watts Max
|
Power input single phase
|
Yes
|
Rated line current
|
15 A per line cord
|
Maximum current
|
54 A peak for 20 ms per line cord
|
Dropout carry through time at minimum voltage
|
20 ms
|
Circuit breaker rating
|
20 A per line cord
|
Power factor correction
|
>0.98 at all loads
|
Ground leakage current (mA)
|
<3.0 (mA) per line cord
|
Electrical input connection
|
IEC309 (16 Amps)
|
Power cords
|
2 (for redundancy)
|
Power input redundancy
|
Yes, with auto failover switch
|
Operating temperature range
|
5 to 35º C
|
Operating humidity range
|
20 to 80% RH
|
Environmental monitoring
|
Air temperature to servers control: Yes; Water-In temperature monitor: Yes
|
Compliance industry standards
|
UL Listing 484; CUL Canadian std. 22.2 No.236; EN61000-3-2; EN61000-3-3 Flicker; EN61000-4-2; EN61000-4-3; EN61000-4-4; EN61000-4-5; EN61000-4-6; EN61000-4-8; EN61000-4-11; CB report to IEC 60950-1; TÜV / GS EN 60335-1 (according to 60335-2-40)
|