The monitored vertical rack mount power distribution units, provides both single and three-phase monitored power, as well as full-rack power utility ranging from 4.9 kVA up to 22 kVA. Available PDU's include full rack models with 39 receptacles or with 78 receptacles, and half rack versions, 3 phase models with 12 C-19 receptacles, and single phase models with 24 C-13 and 3 C-19 receptacles.

Caracteristici

Performance: With both single-phase or three-phase power and output power ranging from 4.9 kVA up to 22.1 kVA per PDU, the amount of equipment connected to a single PDU is significantly increased over existing PDU products available. Additional customer choice of single feed or dual feed models allow for power redundancy as well as increased outlet count (Full rack vertical mount models with either 39 receptacles per single feed model, or 78 receptacles per dual feed model; half rack vertical mount models with twelve C-19 receptacles for 3 phase versions, and single phase versions have 24 C-13 and three C19 receptacles).

Customer choice: Full rack vertical PDU: Models consist of single feed or dual feed models allowing for power redundancy as well as increased outlet count (either 39 receptacles per single feed model or 78 receptacles per dual feed model); Along with the product choices comes the requirement to be sure and have your data center able to accommodate the correct input power. Below are the types of input plugs available on the full rack vertical PDU models; Half rack vertical PDU: Models consist of single feed model with twelve C-19 outlets. Along with the product choices comes the requirement to be sure and have your data center able to accommodate the correct input power. Below are the types of input plugs on the available on the half rack vertical PDU models.

Monitoring: The front panel has a two-digit, seven segment LED digital display, which shows the current in each circuit breaker, a scroll button to scroll through values, and six LEDs, which indicate current overloads and voltage out of range conditions. Current monitoring consists of two digit RMS current, with load segment LEDs reporting three different conditions (normal 0-80%; caution 80-102%; warning > 102%). Voltage monitoring measures over voltage and under voltage on any output load segment.

Color-coded load segments: Both the front panel receptacles and circuit breakers are color coded by load segment for easy and quick identification and matching. Load segments are also spread across the length of the PDU for equal distribution in a rack. Flat rocker circuit breakers provide additional security by preventing accidental shut off (smooth/flush to PDU surface when on).



HP şi-a luat angajamentul de a furniza clienţilor informaţii despre substanţele chimice din produsele sale, respectând cerinţe legale precum REACH (Regulamentul CE Nr. 1907/2006 al Parlamentului European şi al Consiliului). Un raport cu informaţii chimice pentru acest produs este disponibil la adresa: www.hp.com/go/reach.